VELUX roof window for smoke ventilation

Technical details


Introduction

VELUX flat-roof smoke-ventilation windows with integrated motor are CE-marked in compliance with the European standard for smoke and heat exhaust ventilators EN 12101-2.


Flat-roof smoke-ventilation
Window Material Pane Dome EN Norm
CSP Details Details Variants Classification
Product code:
1073Q
PVC Double glazing Polycarbornate
or acrylic
EN 12101-2

Size grid
CSP CSP  
 
100 x 100 120 x 120  

Geometrical pane area Av in m2
CSP CSP  
0.88 130  

Classification in accordance with the parameters of European EN 12101-2
Specifications VELUX smoke-ventilation window
Reliability (Re) Re 1000+10000
Snow load (SL)

SL 1000 (Size 100x100), SL 500 (Size 120x120)

Low Temperature (T) T (-15)
Wind load (WL) WL 3000
Heat Exposure (B) B 300

Aerodynamic area Aa in m2

CSP CSP  
0.42 0.58  

Technical values
Uw-value W/m2K Ug-value W/m2K g-value Tv-value Rw-value
10* 0.9 0.53** 0.72** 37db
* A= 2.79 m2 (u-value according to EN 1873:2005)
**with clear acrylic dome

Guide for wiring

The window and control system
Smoke-ventilation window  
  • Flat-roof smoke-ventilation window with integrated motor and CE marking in compliance with European standard for natural smoke and heat exhaust ventilators EN 12101-2.
  • The window can be opened up to approx. 15 cm for daily comfort ventilation.
  • The smoke ventilation motor is concealed in both open and closed position.
  • When the smoke ventilation function is activated, the window opens to 50 cm.
Control system KFX 210  
  • Control system consisting of control unit (KFC 210) with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 10 amp), additional break-glass point (KFK 100), and smoke detector (KFA 100).
  • CE-marked in compliance with EN 12101-10.
  • Controls up to 4 GGL/GGU smoke-ventilation roof windows or 1 CSP flat-roof smoke-ventilation window.
  • Integrated emergency power supply for 72 hours.
  • In-wall mounting or with frame for on-wall mounting, unit dimensions: 398 x 393 x 127 mm (W x H x D).
  • Colour of control system: White NCS S 1000N
  • Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows.
  • Enables control via external alarm systems, if required.
Control unit KFC 210  
  • Control unit with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 10 amp.).
  • CE-marked in compliance with EN 12101-10.
  • Controls up to 4 GGL/GGU smoke-ventilation roof windows or 1 CSP flat-roof window for smoke ventilation.
  • Integrated emergency power supply for 72 hours.
  • In-wall mounting or with frame for on-wall mounting, control unit dimensions: 398 x 393 x 127 mm (W x H x D).
  • Colour of control system: White NCS S 1000N.
  • Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows.
  • Enables control via external alarm systems, if required.
Control unit KFC 220  
  • Control unit with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 2 x 10 amp.).
  • CE-marked in compliance with EN 12101-10.
  • Controls up to 8 GGL/GGU smoke-ventilation roof windows or 2 CSP flat-roof smoke-ventilation windows.
  • Integrated emergency power supply for 72 hours.
  • In-wall mounting or with frame for on-wall mounting, control unit dimensions: 398 x 393 x 127 mm (W x H x D).
  • Colour of control system: White NCS S 1000N.
  • Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows.
  • Enables control via external alarm systems, if required.
Break-glass point KFK 100  
  • Break-glass point for activating the smoke ventilation function.
  • Colour: Grey (RAL 7047).
  • Dimensions: 125 x 125 x 36 mm (W x H x D).
  • Up to 10 break-glass points can be used with each VELUX control system.
  • Visual and acoustic indication of correct function, error, and alarm.
Comfort switch KFK 200  
  • Wall switch enabling natural ventilation for daily comfort.
  • Colour: White (RAL 1013).
  • Dimensions: 81 x 81 x 12 mm (W x H x D).
  • Up to 10 wall switches can be used with each VELUX control system.
Smoke detector KFA 100  
  • Smoke detector for early fire detection.
  • Colour: White (RAL 9003).
  • Dimensions: 50 x 100 mm (H x D) incl. socket.
  • Up to 10 smoke detectors can be used with each VELUX control system.
  • Visual indication of activation.
Rain sensor KLA 200  
  • Rain sensor for automatic closure of VELUX smoke ventilation windows in case of rain when in comfort ventilation mode).
  • Colour: Dark grey (NCS S 7500-N).
  • Dimensions: 40 x 70 x 13 mm (W x H x D).
  • The rain sensor is overruled in case of fire.